Fire Rated Doors

Fire Door Standards Comparison NFPA 80 vs IS 3614:2021

Topic NFPA 80 (USA) IS 3614:2021 (India) Common Points Key Differences
Scope Covers fire doors, shutters, dampers Covers fire doors, doorsets, frames, sliding & rolling shutters Both regulate fire door safety IS has broader scope; NFPA includes dampers
Fire Rating Integrity only Integrity + Insulation (min 30 min) Both require integrity testing IS requires insulation; NFPA does not
Vision Panel Allowed per listing Strict size limits (0.12m² / 0.06m²) Both allow only tested glazing IS has strict limits; NFPA flexible
Hardware Listed & labeled

mandatory

Hardware must be supplied & certified by door manufacturer Both require certified hardware IS shifts liability to door manufacturer
Undercut Approx 19 mm allowed 19 mm

floor; 9 mm on sill

Both similar limits IS defines sill-specific limits
Intumescent Only if required by listing Mandatory for insulated doors; Smoke seals required Both allow seals IS makes intumescent seals compulsory
Frames Labelled frames; per listing Min 1.2 mm steel; max depth 350 mm Both need approved frames IS has detailed frame specifications
Inspection Annual

mandatory

No fixed annual inspection clause Both require maintenance NFPA mandates annual inspection