There are two staircases having width of 1.16 mt & 1.50 mt for ground & upper loor and two staircases having width of 1.16 mtr & 0.70 mt for basement against the required width of 1.50 mtr each.
The width of corridor is between 1,40 mtr to 1.50 mtr against the required clear cut width of 1.50 mt.
The main exit doors having with of 1.0 mir against the required with of 1.50 mtr & the class room door with is 0.75 mtr against the required width of 1.20 mtr.
Smoke Management System not provided in the basement & upper floors.
First Aid hose reel provided but found not working-
Automatic sprinkler system provided but found not working in the basement.
Terrace level fire fighting pump capacity 450 LPM provided against the required capacity of 900 LPM & the pump is not operation.
Overhead tank capacity 2000 Itr provided against the required capacity 15,000
Exit signage not provided.
- Lift lobby not provided with fire check door not provided in the basement and upper floors,
- Staff seating area in the basement not allowed.
- Classes’ partitions with glass not allowed.